Abstract

In this study, it turned out that the magnitude of Partial Discharges(PD) and the emission of Ozone(O3) were in a strong positive relation by performing insulation diagnostic tests on artificially defect high voltage motor stator
windings. In this sense, the O3 measurements can be a powerful index of the insulation deterioration during normal operation especially in case of surface PD activity.

Abstract 37 | PDF Downloads 40

##plugins.themes.bootstrap3.article.details##

Keywords

PHM

References
Kim, H. D. (2014). Characteristics of Insulation Diagnosis and Failure in Gas Turbine Generator Stator Windings. J. EET, Vol.9, No.1, pp. 280-285. doi:http://dx.doi.org/10.5370/JEET.2014.9.1.280
Kim, H. D., Kong, T. S., Ju, Y.H., & Kim, B. H. (2011). Analysis of Insulation Quality in Large Generator Stator Windings. J. EET, Vol.6, No.2, pp. 384-390. doi:http://dx.doi.org/10.4313/JKEM.2012.25.4.309
Kim, H. D., & Kong, T. S. (2012). Characteristics of Insulation Diagnosis and Failure in 6.6.kV Motor Stator Windings. J. KIEEME, Vol.25, No.4, pp. 309-314. doi:http://dx.doi.org/10.4313/JKEM.2012.25.4.309
Kim, H. D., & Kong, T. S. (2014). Estimation of Insulation Diagnosis and Dielectric Strength in 6.6kV Motor Stator Windings. Trans. KIEE, Vol.63, No.6, pp. 780-785. doi:http://dx.doi.org/10.5370/KIEE.2014.63.6.780
Lépine, L., Lessard-Déziel, D., Bélec, M., Guddemi, C., & Nguyen, D.N.(2007). Understanding ozone distribution inside stator core and measurements inside air-cooled generators to assess partial discharges problems., Iris
Rotating Machine Conference, June 2007. San Antonio, Tx
Millet, C., Nguyen, D.N., Lépine, L., Lessard-Déziel, D., & Guddemi, C.(2008). Case study – high ozone concentration in hydro generators., Proceedings of the 29th Electrical Insulation Conference(pp.178-182), June 2009, Montréal, Canada